top of page

TeSys D contactor, 3 poles (3NO), for motor control applications up to 25A/690V AC-3/3e (11kW@400V). It provides a 230V 50/60Hz AC coil, 1NO+1NC built-in auxiliary contacts (NC mirror certified), connection by screw clamp terminals. For operating rates until 3600 cycles/hour and environments until 60°C, it procures high reliability and durability. Compact (45mm width), DIN-rail mounting or screw fixing. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh)

 

Product Dimensions:

  • L:11cm x W:9cm x H:5cm

LC1D25P7 - Contactor 25A Coil 230VAC by Schneider Electric

Rating is 0.0 out of five stars based on reviews
SKU: C9-6-5
R2 142,99 Regular Price
R2 089,42Sale Price
Only 1 left in stock
  • Motor power kW 5.5 kW at 220...230 V AC 50/60 Hz (AC-3)
    11 kW at 380...400 V AC 50/60 Hz (AC-3)
    11 kW at 415...440 V AC 50/60 Hz (AC-3)
    15 kW at 500 V AC 50/60 Hz (AC-3)
    15 kW at 660...690 V AC 50/60 Hz (AC-3)
    5.5 kW at 400 V AC 50/60 Hz (AC-4)
    5.5 kW at 220...230 V AC 50/60 Hz (AC-3e)
    11 kW at 380...400 V AC 50/60 Hz (AC-3e)
    11 kW at 415...440 V AC 50/60 Hz (AC-3e)
    15 kW at 500 V AC 50/60 Hz (AC-3e)
    15 kW at 660...690 V AC 50/60 Hz (AC-3e)
    Motor power hp 3 hp at 230/240 V AC 50/60 Hz for 1 phase motors
    2 hp at 115 V AC 50/60 Hz for 1 phase motors
    7.5 hp at 230/240 V AC 50/60 Hz for 3 phases motors
    15 hp at 460/480 V AC 50/60 Hz for 3 phases motors
    20 hp at 575/600 V AC 50/60 Hz for 3 phases motors
    7.5 hp at 200/208 V AC 50/60 Hz for 3 phases motors
    Compatibility code LC1D
    Pole contact composition 3 NO
    Contact compatibility M2
    Protective cover With
    [Ith] conventional free air thermal current 10 A (at 60 °C) for signalling circuit
    40 A (at 60 °C) for power circuit 
    Irms rated making capacity 140 A AC for signalling circuit conforming to IEC 60947-5-1
    250 A DC for signalling circuit conforming to IEC 60947-5-1
    450 A at 440 V for power circuit conforming to IEC 60947
    Rated breaking capacity 450 A at 440 V for power circuit conforming to IEC 60947
    [Icw] rated short-time withstand current 240 A 40 °C - 10 s for power circuit
    380 A 40 °C - 1 s for power circuit
    50 A 40 °C - 10 min for power circuit
    120 A 40 °C - 1 min for power circuit
    100 A - 1 s for signalling circuit
    120 A - 500 ms for signalling circuit
    140 A - 100 ms for signalling circuit 
    Associated fuse rating 10 A gG for signalling circuit conforming to IEC 60947-5-1
    63 A gG at <= 690 V coordination type 1 for power circuit
    40 A gG at <= 690 V coordination type 2 for power circuit
    Average impedance 2 mOhm - Ith 40 A 50 Hz for power circuit 
    Power dissipation per pole 3.2 W AC-1
    1.25 W AC-3
    1.25 W AC-3e
    [Ui] rated insulation voltage  Power circuit: 690 V conforming to IEC 60947-4-1
    Power circuit: 600 V CSA certified
    Power circuit: 600 V UL certified
    Signalling circuit: 690 V conforming to IEC 60947-1
    Signalling circuit: 600 V CSA certified
    Signalling circuit: 600 V UL certified
    Overvoltage category III
    Pollution degree 3
    [Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947
    Safety reliability level B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
    B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
    Mechanical durability 15 Mcycles
    Electrical durability 1.65 Mcycles 25 A AC-3 at Ue <= 440 V
    1.4 Mcycles 40 A AC-1 at Ue <= 440 V
    1.65 Mcycles 25 A AC-3e at Ue <= 440 V
    Control circuit type AC at 50/60 Hz standard
    Coil technology Without built-in suppressor module
    Control circuit voltage limits 0.3...0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz
    0.8...1.1 Uc (-40…60 °C):operational AC 50 Hz
    0.85...1.1 Uc (-40…60 °C):operational AC 60 Hz
    1...1.1 Uc (60…70 °C):operational AC 50/60 Hz
    Inrush power in VA 70 VA 60 Hz cos phi 0.75 (at 20 °C)
    70 VA 50 Hz cos phi 0.75 (at 20 °C)
    Hold-in power consumption in VA 7.5 VA 60 Hz cos phi 0.3 (at 20 °C)
    7 VA 50 Hz cos phi 0.3 (at 20 °C)
    Heat dissipation 2…3 W at 50/60 Hz
    Operating time 12...22 ms closing
    4...19 ms opening
    Maximum operating rate 3600 cyc/h 60 °C
    Connections - terminals Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable end
    Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable end
    Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable end
    Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end
    Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without cable end
    Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without cable end
    Power circuit: screw clamp terminals 1 2.5…10 mm² - cable stiffness: flexible without cable end
    Power circuit: screw clamp terminals 2 2.5…10 mm² - cable stiffness: flexible without cable end
    Power circuit: screw clamp terminals 1 1…10 mm² - cable stiffness: flexible with cable end
    Power circuit: screw clamp terminals 2 1.5…6 mm² - cable stiffness: flexible with cable end
    Power circuit: screw clamp terminals 1 1.5…10 mm² - cable stiffness: solid without cable end
    Power circuit: screw clamp terminals 2 2.5…10 mm² - cable stiffness: solid without cable end 
    Tightening torque  Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
    Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
    Power circuit: 2.5 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
    Power circuit: 2.5 N.m - on screw clamp terminals - with screwdriver Philips No 2
    Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
    Power circuit: 2.5 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
    Auxiliary contact composition 1 NO + 1 NC
    Auxiliary contacts type  Type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
    type mirror contact 1 NC conforming to IEC 60947-4-1
    Signalling circuit frequency 25...400 Hz
    Minimum switching voltage 17 V for signalling circuit
    Minimum switching current 5 mA for signalling circuit 
    Insulation resistance > 10 MOhm for signalling circuit 
    Non-overlap time 1.5 ms on de-energisation between NC and NO contact
    1.5 ms on energisation between NC and NO contact 
    Mounting support  Rail
    Plate
No Reviews YetShare your thoughts. Be the first to leave a review.

RELATED PRODUCTS

bottom of page